Square D. B40266-483-01 Panelboard

Cost to be determined

You can still order this product.

Will contact you with a price before your final purchase.

Refurbished
1 in stock
Equipment Ground Bar Kits for Panelboard Types HC-(I-Line) and QMB use 60 °C or 75 °C Copper or Aluminum Wire / Extension Kit I-Line Type HCN, HCM, and HCW Panelboards

Features
  • (Panelboard ) / (Use Ground Bar Kit Catalog No.)
  • I-Line - HCN / PK-27GTA
  • I-Line - HCM, HCW, or HCWM / PK-32DGTA
  • QMB / PK-32DGTA
  • (Wire Range and Recommended Torque)
  • (Wire Range) / (Recommended Torque Inch Pound)
  • Bars With One Hole Ball Size No. 14-10 CU or No. 12-10 AL / 20 Lbs. No. 8 CU - AL / 25 Lbs. No. 6-4 CU - AL / 35 Lbs. Two-No. 14 or No.12 CU / 25 Lbs. Two-No. 12 or No.10 AL / 25 Lbs.
  • Bars With Two Hole Sizes Small Hole - No.14-8 CU or No.12-8 AL / 25 Lbs. Two. No.14 or No.12 CU / 25 lbs. Two. No.12 or No.10 AL / 25 Lbs.
  • Large Hole - No.14-4 CU or No.12-4 AL/ 35 Lbs. Two. No.14 or No.12 CU / 35 lbs. Two. No.12 or No.10 AL / 35 Lbs.
  • Large Lug. No.4-2/0 CU-AL / 110 Lbs. I-Beam Lug. 6-300 MCM CU-AL / 275 Lbs.
  • Wire Range and Torque for 1600 Amp Ground Bar Kit. (Factory Installed On QMB Interiors) Wire Range / Recommended Torque Inch Pounds No.3/0 -500 MCM CU-AL / 340 Lbs.
  • Ground Bar Kit Mounting Instructions Minimum Spacing Required Between Live Parts and Grounded Metal Parts (Voltage: 250 or Less 251-600) / (Through Air and Over Surface: Half Inch , One Inch)
  • (For the Panelboards B80043-162-01)
  • Catalog No. HC-2609-EX(*) / For Use With : HC- -26B Series E-1 Boxes
  • Catalog No. HC-3209-EX(*) / For Use With : HC- -32BB Series E-1 Boxes
  • Catalog No. HC-4212-EX (*) / For Use With : HC- -42DB Series E-1 Boxes


Miscellaneous